Description
The full range comprises:
- Commercial (to CISPR16), up to 16A, single phase.
- Commercial (to CISPR16), up to 100A, 2 and 4 line.
- Military (Def Stan 59-41) and Mil Spec 461 types
- Automotive, to CISPR25
- Voltage probe to CISPR16
Features
All commercial LISNs include an artificial hand connection and a transient limiter. This adds a 30dB insertion loss. A 30dB pre-amplifier is included which can be connected in the RF output feed to return the insertion loss to 0dB.
All bar the heavy current LISNs are constructed in a flanged aluminium enclosure that can be bolted directly down to a ground plane (as required by standards). The underside of the enclosure is left unpainted to ensure good conductivity with the plane.
The 16A and military/automotive LISNs have an RF output for each line, thus allowing parallel measurements of the emissions. This facilitates measurement of common mode and differential mode components of the emissions if required.
Key Points
- LISNs with ratings up to 100A/line and up to 4 lines.
- Commercial versions fully compliant to CISPR16
- Def Stan and Mil Spec versions also available
- Voltage probe (PLIP) with inbuilt safety features for lines >100A
- Fully calibrated and complete with test lab certificate and cal. data
SPECIFICATION FOR CISPR16 LISN - up to 32 amps | |||
LISN16A1P (*LISN-A-16A1P) | LISN32A1P | LISN32A3P | |
Cont.amps (per ph) | 16 Amps | 32 Amps | 32 Amps |
Input connection | 2m flying lead | 4mm socket | 4mm socket |
Output connections | Mains socket + 4mm socket | 4mm socket | 4mm socket |
Power frequency | DC to 400 Hz | DC to 400Hz | DC to 400Hz |
RF out selection | separate BNCs | Selector switch | Selector switch |
Max voltage (Ref. to ground) | 275v rms | 275v rms | 275v rms |
Insertion loss, Pre-amp bypassed | 30dB | 30dB | 30dB |
Network | 50Ω II 50μH | 50Ω II 50μH | 50Ω II 50μH |
Impedance | To CISPR16, figure 7b, ±20% | To CISPR16, figure 7b, ±20% | To CISPR16, figure 7b, ±20% |
Construction | Alloy case with base flanges | Modular instrument case | Modular instrument case |
Pre-amp gain | 30dB, ± 1.5dB | 30dB, ± 1.5dB | 30dB, ± 1.5dB |
Pre-amp location | external | internal | internal |
Frequency range | 150KHz-30MHz 9KHz-30MHz* |
150KHz-30MHz | 150KHz-30MHz |
Noise figure | less than 5dB | less than 5dB | less than 5dB |
Max signal level | +80dBμV | +80dBμV | +80dBμV |
Saturation signal level | +120dBμV | +120dBμV | +120dBμV |
Power | 12V DC from included mains supply | 12V DC from included mains supply | 12V DC from included mains supply |
MODEL | STANDARD | CURRENT RATING (A) |
PHASES | TRANSIENT LIMITER FITTED | SIZE | FREQUENCY RANGE |
LISN16A1P | CISPR16 | 16 | L, N | YES | A | 150KHz - 30MHz |
LISN-A-16A1P | CISPR16 |
16 | L, N | YES | D | 9KHz - 30MHz |
LISN32A1P | CISPR16 | 32 | L, N | YES | B | 150KHz - 30MHz |
LISN63A1P | CISPR16 | 63 | L, N | YES | B | 150KHz - 30MHz |
LISN100A1P | CISPR16 | 100 | L, N | YES | B | 150KHz - 30MHz |
LISN32A3P | CISPR16 | 32 | L1, L2, L3, N | YES | C | 150KHz - 30MHz |
LISN63A3P | CISPR16 | 63 | L1, L2, L3, N | YES | C | 150KHz - 30MHz |
LISN100A3P | CISPR16 | 100 | L1, L2, L3, N | YES | C | 150KHz - 30MHz |
LISNC25/25A1P | CISPR25 | 25 | 1 | NO | A | 100KHz - 108MHz |
LISNC25/25A2P | CISPR25 | 25 | 2 | NO | A | 100KHz - 108MHz |
LISNC25/100A | CISPR25 | 100 | 1 | NO | D | 100KHz - 108MHz |
LISN59-41/32A2P | DEFSTAN59-41 | 32 | 2 | NO | A | 20Hz - 400MHz |
LISN59-41/100A | DEFSTAM59-41 | 100 | 1 | NO | D | 20Hz - 400MHz |
LISN461E/10A2P | MIL 461E | 10 | 2 | NO | E | 10KHz - 10MHz |
LISN461E/100A | MIL 461E | 100 | 1 | NO | E | 10KHz - 10MHz |
MECHANICAL DATA - Size in mm | |||||
CASE | A | B | C | D | E |
WIDTH | 180 | 530 | 535 | 180 | 200 |
LENGTH | 300 | 422 | 522 | 500 | 600 |
HEIGHT | 80 | 310(6u) | 445(9u) | 100 | 185 |
Voltage Probe (Power line Interference Probe: PLIP)
The Voltage Probe requirement is covered by our PLIP (Power Line Interference Probe). This fully meets the requirements of CISPR16, but has additional features:
-
-
- Fully galvanic isolation between input and output (>1kV), for the safety of operator and analyser!
- Shrouded safety clips for attachment to the line to be measured.
- Filtered frequency response matched to Band A and B.
- Current limiting on the output.
- Visual indication of high voltage input.
-